6 Vector Control and Applied Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-8
PM Motor Mode
6
6-
8-6 Adjustment of PM Motor
Mode Settings
Precautions for Correct Use
• Changing the PM Motor Capacity (H103)/PM Motor Pole Number (H104) automatically
changes the values set in A003, A004, and H105 to H110. Be sure to set the PM Motor
Capacity (H103)/PM Motor Pole Number (H104) first before setting other motor parameters.
To use PM motor control, perform offline auto-tuning for the PM motor parameters.
If you cannot perform auto-tuning, set the motor parameters appropriately according to
6-8-5 PM Motor
Parameter Settings
on page 6-61.
This section describes how to adjust the parameter settings if the inverter cannot provide sufficient per-
formance characteristics after auto-tuning or motor parameter settings.
For the adjustment of PM motor control, this inverter provides parameters for the control during startup,
stableness/responsiveness parameters, and initial pole position estimation functions as shown in the
table below.
For how to adjust these parameters, refer to the next section, PM Motor Adjustment.
H109
PM Motor Parameter Ke
0001 to 9999 (0.0001 to 0.9999)
1.000 to 6.553
Dependent
on capacity
Vp/
(rad/s)
H110
PM Motor Parameter J
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Dependent
on capacity
kgm
2
6-8-6
Adjustment of PM Motor Mode Settings
PM Motor Adjustment Parameters
Parameter
No.
Function name
Data
Default
data
Unit
b083
Carrier Frequency
2.0 to 15.0
10.0
kHz
H106
PM Motor Parameter R
0.001 to 65.53
Dependent
on capacity
Ω
H111
PM Motor Parameter R
(Auto-tuning Data)
H107
PM Motor Parameter Ld
0.01 to 655.3
Dependent
on capacity
mH
H112
PM Motor Parameter Ld
(Auto-tuning Data)
H108
PM Motor Parameter Lq
0.01 to 655.3
Dependent
on capacity
mH
H113
PM Motor Parameter Lq
(Auto-tuning Data)
H116
PM Motor Speed Response
1 to 1000
100
%
H117
PM Motor Starting Current
20.00 to 100.0
70.00
%
H118
PM Motor Starting Time
0.01 to 60.00
1.00
s
H119
PM Motor Stabilization Parameter
0 to 120
100
%
H121
PM Motor Minimum Frequency
0.0 to 25.5
8.0
%
H122
PM Motor No-Load Current
0.00 to 100.0
10.00
%
H123
PM Motor Starting Method Selection
00:
Disabled
00
−
01:
Initial pole position estima-
tion enabled
Parameter
No.
Function name
Data
Default
data
Unit
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...