DS1-BD (DS1 Interface Circuit Pack)
Issue 1 May 2002
8-597
555-233-143
NPE Connection Audit Test (#50):
The system sends a message to the on-board microprocessor to update the
network connectivity translation for all the Network Processing Elements (NPEs)
on the circuit pack.
Table 8-241.
Test #50 NPE Connection Audit Test
Error
Code
Test
Result
Description / Recommendation
None,
2100
ABORT
System resources required for this test are not available.
1019
ABORT
Test already in progress.
FAIL
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
PASS
The circuit pack’s NPEs have been updated with their translation.
0
NO
BOARD
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
1. Verify that the board’s translations are correct. Use the add ds1 UUCSS
command to administer the DS1 interface if it is not already administered.
2. If board was already administered correctly, check the error log to
determine whether the board is hyperactive. If so, the board was shut
down. Reseating the board will re-initialize it.
3. Issue the busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...