Maintenance-Object Repair Procedures
555-233-143
8-116
Issue 1 May 2002
PASS
The station is connected properly to the switch. Investigate user-reported
troubles on this port by running other port tests, by examining station wiring, or
by inspecting the station.
NOTE:
This test may also pass if no terminal equipment is connected and the
terminal is located very far from the switch.
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This result could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to make sure that the board translations are correct. Use the list
configuration command, and resolve any problems.
2. If the board is correctly inserted, issue the busy board UUCSS command.
3. Issue the reset board UUCSS command.
4. Issue the release board UUCSS command.
5. Issue the test board UUCSS long command.
This should re-establish the link between the internal ID and the port. If
not, verify that a valid board is inserted.
Table 8-44.
Test #48 Station Present Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...