Maintenance-Object Repair Procedures
555-233-143
8-422
Issue 1 May 2002
Receive FIFO Overflow Error Counter
Test (#596)
This test is nondestructive. When the C-LAN circuit pack detects packet-bus
buffer overflow, it increments the error on the FIFO Overflow error counter. This
test reads and clears the counter.
If errors are:
Then they may be due to:
Occasional
Statistical buffer sizing
Persistent
Circuit pack congestion that requires redistribution of traffic load
Table 8-170.
Test #596 Receive FIFO Overflow Error Counter Test
Error
Code
Test
Result
Description / Recommendation
2000
ABORT
Did not receive circuit pack test response within the allowable time period.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, reset the circuit pack (reset board UUCSS).
3. If the problem persists, replace the circuit pack.
2100
ABORT
Could not allocate the necessary system resources to run test.
2500
ABORT
Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
1–10
FAIL
Circuit pack detects overflow errors. The error code indicates the value of the
on-board error counter.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to fail, execute Packet Interface Test #598 (test board
UUCSS).
3. If Packet Interface Test #598 fails, see
‘‘PKT-BUS (Packet Bus)’’ on page
for repair procedures.
PASS
Circuit pack detects no errors.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...