Maintenance-Object Repair Procedures
555-233-143
8-1810
Issue 1 May 2002
UPS (Server UPS)
The UPS MO supports the UPS device for each S8700 Media Server. This MO’s
maintenance software reacts to UPS-generated inline errors via SNMP traps.
NOTE:
This MO provides no periodic or on-demand tests.
Server UPS Alarms
The following table contains the various UPS-generated SNMP alarms/traps.
Table 8-692.
Server’s SNMP Traps
Enterprise Specific Trap and
Event Numbers
Definition of Traps
Trap #6, Event ID #6
Alarm string = #1, ACT, UPS, A, 6, SUP, power failure: Shutting
down in 3 minutes.
If the event ID is 6, the UPS battery’s power is in a critically low
condition, with an estimated 3 minutes of remaining holdover.
■
A warning is written to every logged-in user of the server.
■
When 3 minutes elapse, the server begins shutting down.
Trap #7, Event ID #7
Alarm string = #1, ACT, UPS, A, 7, SUP, power failure: Shutting
down in 4 minutes.
The UPS battery’s power is in a critically low condition, with an
estimated 4 minutes of remaining holdover.
■
A warning is written to every logged-in user of the server.
■
When 4 minutes elapse, the server begins shutting down.
Trap #8, Event ID #8
Alarm string = #1, ACT, UPS, A, 7, SUP, power failure: Shutting
down in 5 minutes.
The UPS battery’s power is in a critically low condition, with an
estimated 5 minutes of remaining holdover.
■
A warning is written to every logged-in user of the server.
■
When 5 minutes elapse, the server begins shutting down.
Trap #4, Event ID #9
upsAlarmOnBattery
Alarm string = #1, ACT, UPS, A, 9,WRN, Miscellaneous trap, e.g.,
bad battery.
This UPS trap [Event #9] is a miscellaneous environmental alarm
sent from the UPS that supports server A. For example, the battery
may be bad and should be replaced.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...