IPMEDPRO (IP Media Processor Circuit Pack)
Issue 1 May 2002
8-943
555-233-143
24576–
24580
FAIL
An ETHERNET device failed:
1. Issue the busyout board UUCSS command.
2. Issue the reset board UUCSS command.
3. Issue the release board UUCSS command.
4. Issue the test board UUCSS long command.
If the board continues to fail replace the board.
PASS
The FPGA device on this TN2302 is operating correctly.
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This could be
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Ensure that the board translations are correct. Administer the
IPMEDPRO interface if it is not already administered.
2. If the board was already administered correctly, check the error log to
determine whether the board is hyperactive. If this is the case, the board
is shut down. Reseating the board re-initializes the board.
3. If the board was found to be correctly inserted in step 1, then issue the
busyout board UUCSS command.
4. Issue the reset board UUCSS command.
5. Issue the release board UUCSS command.
6. Issue the test board UUCSS long command.
This should re-establish the linkage between the internal ID and the port.
Table 8-366.
Test #1406 MP Diagnostic Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...