Maintenance-Object Repair Procedures
555-233-143
8-1548
Issue 1 May 2002
Notes for SYSTEM Error 605 AUX Data:
1. From the Linux command line, execute the almdisplay command, and
follow the troubleshooting procedures listed there for “media server
alarms.” After fixing that problem, try the interchange again.
2. Mass Storage System is in use. Check disk for activity. Wait until every
MSS activity completes, then retry the interchange again. If the problem
persists, check for alarms and errors against MSS components.
3. Test the PKT-INT on both carriers with the long test sequence. Follow
procedures for “PKT-INT”. Once every test of both PKT-INTs passes, try
the interchange again.
4. Consult SW-CTL service documentation. Test SW-CTL on both carriers
with the long test sequence. Follow repair instructions for any failures.
Once every test of both SW-CTLs passes, try the interchange again.
5. Make sure the standby server is refreshed, then try the interchange again.
6. Examine alarm log to determine which of the PKT-INT or SYSAM circuit
packs has a minor alarm against it. Consult the section in this chapter for
that circuit pack.
7. Run test duplication-interface long, and follow instructions for any test
that does not pass.
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...