EMG-XFER (Emergency Transfer)
Issue 1 May 2002
8-737
555-233-143
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests:
Descriptions and Error Codes (Multicarrier)
Always investigate tests in the order presented in the table below. For example,
by clearing error codes associated with the Battery and Battery Charger Query
test (#5), you may also clear errors generated from other tests in the testing
sequence.
Table 8-286.
EMG-XFER Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
0
1
1.
Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0
Any
Any
Any
test environment UU
1
0
Emergency Transfer query
(#124)
MAJOR
ON
test environment UU r
3
257
0
Emergency Transfer query
(#124)
WARNING
ON
test environment UU r
3