FIBER-LK (Fiber Link)
Issue 1 May 2002
8-861
555-233-143
Failure Audit (#777)
This test is nondestructive.
This test queries the SNI(s) on the fiber link for any existing failures and any
unacknowledged cleared failure messages. Each failure generates an error and
alarm entry against SNI-BD, SNI-PEER, or FIBER-LK. An unacknowledged
cleared failure message is a message the SNI circuit pack sent to software
indicating a previous failure is now gone and the SNI circuit pack did not receive a
message from software indicating that the failure message was received by
software.
If no failures are detected by the SNI circuit pack, this test will pass.
If this test reports failures, the results screen for the test fiber-link command will
show FAIL with no FAIL code. The error log must then be displayed via display
errors with category PNC to view SNI-BD and FIBER-LK errors and display
errors with category PNC-PEER to view SNI-PEER errors.
For EI-to-EI fiber links, this test is not run. For EI-to-SNI fiber links, this test is run
on the SNI circuit pack endpoint of the fiber link. For SNI-to-SNI fiber links, this
test is run on both SNI circuit pack endpoints of the fiber link.
Table 8-330.
Test #777 Failure Audit
Error
Code
Test
Result
Description / Recommendation
2100
ABORT
Could not allocate the necessary system resources to run this test.
2300
ABORT
The downlink message necessary to run this test could not be sent.
2301
ABORT
The software timer could not be set before sending the downlink message
necessary to run this test.
2302
ABORT
The SNI circuit pack claims that it received a bad message from software.
2303
ABORT
The SNI circuit pack claims that the test requested by software is invalid.
2304
ABORT
SNI firmware is not able to run the test.
1. Retry the command at 1-minute intervals up to 3 times.
Continued on next page
Summary of Contents for S8700 Series
Page 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Page 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Page 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Page 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Page 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Page 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...