Representation of analog values
B.4 Representation of analog values for resistance thermometer
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
50
Equipment Manual, 08/2021, A5E32350124-AG
Table B- 6
Resistance thermometer Ni 100 standard
Ni x00
standard in
°C
(1 digit =
0.1 °C)
Values
Ni x00
standard in
°F
(1 digit =
0.1 °F)
Values
Ni x00
standard
in K
(1 digit =
0.1 K)
Values
Range
Dec.
Hex.
Dec.
Hex.
Dec.
Hex.
>295.0
32767
7FFF
>563.0
32767
7FFF
>568.2
32767
7FFF
Overflow
295.0
:
250.1
2950
:
2501
B86
:
9C5
563.0
:
482.1
5630
:
4821
15FE
:
12D5
568.2
:
523.3
5682
:
5233
1632
:
1471
Overrange
250.0
:
-60.0
2500
:
-600
9C4
:
FDA8
482.0
:
-76.0
4820
:
-760
12D4
:
FD08
523.2
:
213.2
5232
:
2132
1470
:
854
Nominal range
-60.1
:
-105.0
-601
:
-1050
FDA7
:
FBE6
-76.1
:
-157.0
-761
:
-1570
FD07
:
F9DE
213.1
:
168.2
2131
:
1682
853
:
692
Underrange
<-105.0
-32768 8000
<-157.0
-32768 8000
<168.2
32768
8000
Underflow
Table B- 7
Resistance thermometer Ni 100 climatic
Ni x00 climatic in °C
(1 digit = 0.01 °C)
Values
Ni x00 climatic in °F
(1 digit = 0.01 °F)
Values
Range
Dec.
Hex.
Dec.
Hex.
>155.00
32767
7FFF
>311.00
32767
7FFF
Overflow
155.00
:
130.01
15500
:
13001
3C8C
:
32C9
311.00
:
266.01
31100
:
26601
797C
:
67E9
Overrange
130.00
:
-60.00
13000
:
-6000
32C8
:
E890
266.00
:
-76.00
26600
:
-7600
67E8
:
E250
Nominal range
-60.01
:
-105.00
-6001
:
-10500
E88F
:
D6FC
-76.01
:
-157.00
-7601
:
-15700
E24F
:
C2AC
Underrange
<-105.00
-32768
8000
<-157.00
-32768
8000
Underflow
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......