Functions
5.10 Standard machine projects
PROFINET with STEP 7
268
Function Manual, 05/2021, A5E03444486-AL
Rules for the call sequence of "ReconfigIOSystem"
•
Always supply the instruction "ReconfigIOSystem" with the same control data record
(CTRLREC input parameter)!
•
Call sequence following POWER OFF -> POWER ON transition:
–
ReconfigIOSystem call with MODE 1 (optional).
–
ReconfigIOSystem call with MODE 2 (mandatory, even without previous
reconfiguration!).
–
ReconfigIOSystem call with MODE 3 (mandatory).
•
Call sequence following STOP > RUN transition:
–
ReconfigIOSystem call with MODE 1 (optional).
–
ReconfigIOSystem call with MODE 2 (mandatory, even when configuration was
modified in STOP state). Otherwise not required).
–
ReconfigIOSystem call with MODE 3 (mandatory).
•
Call sequence for reconfiguration in RUN state:
–
ReconfigIOSystem call with MODE 1 (mandatory).
–
ReconfigIOSystem call with MODE 2 (mandatory).
–
ReconfigIOSystem call with MODE 3 (mandatory).
Explanations and recommendations concerning the rules
•
If you do not list an IO device to be configured as optional IO device in the control data
record or data block resp. this IO device does not form part of the configuration and does
not take part in data exchange with the CPU.
•
If you do not activate any optional IO device at all and work with the loaded configuration
without reconfiguration, you still have to follow the proceeding described in the above
section and transmit the control data record to the CPU.
The control data record has the simple structure with the following tags:
–
Version (High Byte =1, Low Byte = 0)
–
Number of optional devices to be activated = 0
–
Number of port interconnections that are set in the user program = 0
•
Following a STOP > RUN transition and following a POWER-OFF > POWER-ON transition, all
IO devices are deactivated automatically. For this reason, no ReconfigIOSystem call with
MODE 1 is required for configuration control to function properly.
If you use your project as a universally valid sample for programming the configuration
control, we still recommend to perform the ReconfigIOSystem call with MODE 1 prior to
any reconfiguration. This way, the sample can also be used for reconfigurations in RUN
mode.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......