Functions
5.5 Real-time communication
PROFINET with STEP 7
202
Function Manual, 05/2021, A5E03444486-AL
5.5.7
Setup recommendations for optimizing PROFINET
Optimizing PROFINET with RT
PROFINET provides you with high-performance communication on all levels.
The following figures shows an example of an optimized PROFINET topology.
Figure 5-55 Optimized PROFINET topology
When setting up your PN network topology, take care that the various automation
applications are distributed among separate network branches so that a sufficient bandwidth
reserve will be available for future expansions.
•
If you integrate standard Ethernet devices into the network topology or use standard
Ethernet communication, take into account the network load caused by standard Ethernet
and adapt the network topology as appropriate (max. bandwidth 100 Mbps).
•
For communication with higher-level networks with a high data volume, use the most
direct paths possible to the higher-level network infrastructure.
Also observe the Installation Guideline (
http://www.profibus.com/nc/download/installation-
guide/downloads/profinet-installation-guide/display/
) of the PROFIBUS User Organization.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......