Interrupts/diagnostic messages/diagnostics
6.5 Fault types, causes, and corrective measures
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
74
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
Event ID
Diagnostic
message
F-DI 4/F-DQ 2
Fail-Safe
module
Description
Possible causes
Corrective measures
1
16x0106 Short-circuit to
ground
F-DI 4/F-DQ 2
digital outputs
The fail-safe module
detects a channel
problem where the
M-switch output ter-
minal is unexpectedly
at M potential
•
Short-circuit of
output to M,
ground, or another
channel
•
Defective output
driver
•
"Maximum read-
back time" value is
configured too
small
•
Eliminate the short-
circuit
•
Increase readback
time
•
Replace the fail-
safe module
16x011B Invalid/
inconsistent
firmware present
Module
Inconsistency between
bus ASIC firmware and
fail-safe controller
firmware.
A firmware update
operation was per-
formed using an up-
date file not suitable
for the module (incor-
rect article number or
hardware revision)
•
The firmware up-
date operation
should be repeated
with a suitable up-
date file
•
Replace the fail-
safe module
16x013E Diagnostic event
queue overflow
Module
Overflow of the diag-
nostic events queue
has occurred. A newly-
occurred diagnostic
event could not be
queued for transmis-
sion to the CPU be-
cause the buffer is full.
This can happen if
channel errors come
and go very quickly
(for example, discrep-
ancy errors)
Examine the Diagnos-
tics buffer to see what
errors are occurring,
then address that issue
16x0300 Discrepancy fail-
ure, channel state
0/0
F-DI 4/F-DQ 2
digital inputs
External discrepancy
failure: Channel state
0/0 with 1oo2 none-
quivalent configura-
tion
•
Process signal
faulty, sensor may
be defective
•
Configured dis-
crepancy time too
short
•
Short-circuit
•
Sensor mechanical
activation or
alignment out of
tolerance
•
Check the process
signal, replace sen-
sor if necessary
•
Check the config-
ured discrepancy
time
•
Check the wiring
•
Check that both
sensors are mount-
ed and aligned to
be activated to-
gether
16x0301 Discrepancy fail-
ure, channel state
0/1
F-DI 4/F-DQ 2
digital inputs
External discrepancy
failure: Channel state
0/1 with 1oo2 equiva-
lent configuration
16x0302 Discrepancy fail-
ure, channel state
1/0
F-DI 4/F-DQ 2
digital inputs
External discrepancy
failure: Channel state
1/0 with 1oo2 equiva-
lent configuration
16x0303 Discrepancy fail-
ure, channel state
1/1
F-DI 4/F-DQ 2
digital inputs
External discrepancy
failure: Channel state
1/1 with 1oo2 none-
quivalent configura-
tion
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......