Communication with the redundant system S7-1500R/H
14.1 System IP addresses
Communication
Function Manual, 05/2021, A5E03735815-AJ
411
Communication via the system IP addresses X1 and X2
If the CPUs of the redundant system S7-1500R/H have two PROFINET interfaces (X1 and X2),
you can use the a system IP address for each PROFINET interface. PROFINET devices which are
connected to the interfaces X1 of the CPUs communicate via the system IP address X1.
PROFINET devices which are connected to the interfaces X2 of the CPUs communicate via the
system IP address X2.
①
Open User Communication between the S7-1500R/H redundant system and a different CPU.
②
HMI communication with the S7-1500R/H redundant system
③
Open User Communication between the S7-1500R/H redundant system and a PC
Figure 14-3 Example: Communication of the S7-1515R redundant system via the system IP addresses
X1 and X2