Supported functions
7.1 Calibrating analog modules
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
111
7.1.3
Canceling a calibration
Requirement
●
You have opened the "Online & Diagnostics" view for the selected analog module from
the shortcut menu of the project and you are now in the "Functions > Calibration" area.
●
The associated CPU is online.
●
A calibration is currently running on the analog module.
Procedure
Click the "Cancel" button to cancel an ongoing calibration.
Result
The active calibration is canceled. The channel to be calibrated will then have the same
settings as before the start of calibration.