PROFINET with the redundant S7-1500R/H system
6.7 Configuring PROFINET IO on a redundant S7-1500R/H system
PROFINET with STEP 7
300
Function Manual, 05/2021, A5E03444486-AL
6.7
Configuring PROFINET IO on a redundant S7-1500R/H system
PROFINET IO configurations with the redundant S7-1500R/H system
The following figures show you examples of PROFINET IO configurations with the redundant
S7-1500R/H system.
All the figures use the following abbreviations for AR:
•
SR-AR: System redundancy AR between an IO device (S2) and one of the CPUs of the
redundant S7-1500R/H system
•
AR: "normal" AR between a standard IO device and the associated IO controller
All configurations use the CPU 1515R as an example. The PROFINET configurations shown
also work with the CPU 1513R and CPU 1517H.
IO devices in the PROFINET ring
The redundant S7-1500R system consists of the two CPUs 1515R and two IO devices in the
PROFINET ring. The IO devices support system redundancy S2, media redundancy and
H-Sync Forwarding.
Figure 6-4
Example of a S7-1500R redundant system with two IO devices in the PROFINET ring