Technical specifications
6.1 Technical specifications
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
40
Equipment Manual, 08/2021, A5E48753535-AB
Article number
6ES7144-5KD50-0BA0
Analog inputs
Number of analog inputs
4
•
For voltage measurement
4
•
For resistance/resistance thermometer meas-
urement
4
•
For thermocouple measurement
4
permissible input voltage for voltage input (de-
struction limit), max.
15 V
Constant measurement current for resistance-
type transmitter, typ.
230 ... 300 µA
Cycle time (all channels), min.
90 ms
Technical unit for temperature measurement
adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges (rated values), voltages
•
-80 mV to +80 mV
Yes; 16 bit incl. sign
–
Input resistance (-80 mV to +80 mV)
10 M
Ω
Input ranges (rated values), thermocouples
•
Type B
Yes; 16 bit incl. sign
–
Input resistance (Type B)
10 M
Ω
•
Type C
Yes; 16 bit incl. sign
–
Input resistance (Type C)
10 M
Ω
•
Type E
Yes; 16 bit incl. sign
–
Input resistance (Type E)
10 M
Ω
•
Type J
Yes; 16 bit incl. sign
–
Input resistance (type J)
10 M
Ω
•
Type K
Yes; 16 bit incl. sign
–
Input resistance (Type K)
10 M
Ω
•
Type L
Yes; 16 bit incl. sign
–
Input resistance (Type L)
10 M
Ω
•
Type N
Yes; 16 bit incl. sign
–
Input resistance (Type N)
10 M
Ω
•
Type R
Yes; 16 bit incl. sign
–
Input resistance (Type R)
10 M
Ω
•
Type S
Yes; 16 bit incl. sign
–
Input resistance (Type S)
10 M
Ω
•
Type T
Yes; 16 bit incl. sign
–
Input resistance (Type T)
10 M
Ω
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......