Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
56
Function Manual, 11/2019, A5E33454822-AC
Error code
Meaning
Solution
(DW#16#...)
10060000
No TIO module found.
Possible cause:
The module configured using the hardware identifier is not
a TIO module.
•
Make sure that the configured module is a
TIO module.
•
Check the value at the HWID input
parameter. Specify the hardware identifier of
the TIO module from its module properties
in the hardware configuration.
10070000
An internal error occurred during the address calculation. Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO
module from its module properties in the
hardware configuration. An internal system
constant of data type Hw_SubModule is
available for the symbolic addressing.
x0080000
TIO module is not synchronized using the TIO_SYNC
instruction.
The error code can also indicate that:
•
A job was already present before the first run of the
instruction.
•
The assigned number at the Channel input parameter
is not a digital output.
Check the instruction TIO_SYNC.
10090000
The read cycle time of the isochronous OB is LT#0ms or
has as negative value and is therefore invalid. Correct the
value.
The instruction can only be used without errors in an
isochronous OB.
•
Correct the cycle time.
•
Make sure that TIO_DQ is called in a
"Synchronous Cycle" or "MC-PostServo"
OB.
100A0000
The time T
O
of the TIO model stored in TIO_SYNC_Data
is outside the permissible range of 0 < T
o
<= 4 ms.
Check the instruction TIO_SYNC.
100Bxxxx
An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from RD_ADDR.
Read the description of the RD_ADDR in the
STEP 7 (TIA Portal) information system.
000C0000
One or both time stamps at the TimeStampRE and
TimeStampFE input parameters are invalid. The error is
only signaled for the duration of one application cycle.
Check the TimeStampRE and TimeStampFE
input parameters.
000D0000
The Quality Information of the digital output indicates that
an error has occurred at the digital output.
•
Check the parameter assignment of the
digital output.
•
Check the supply voltage L+/1L+/2L+.
•
Check the wiring of the digital output for
short-circuit, overload, and overtemperature.
000E0000
The number configured at the Channel input parameter is
not a digital output configured as Timer DQ.
•
Check the channel configuration (only for
TM Timer DIDQ 16x24V).
•
Check the operating mode of the digital
output.
100F0000
The read cycle time of the OB of type "Synchronous
Cycle" is too long: T
APP
> 16 ms.
Configure a smaller multiple of the send clock
as the cycle time.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......