Parameters/address space
4.3 Address space
Digital input/digital output module DIQ 4+DQ 4x24VDC/0.5A 4xM12 (6ES7143-5AF00-0BA0)
20
Equipment Manual, 08/2021, A5E36683613-AB
Evaluating the value status
An additional two bytes are occupied in the input address space if you enable the value status
for the digital input/digital output module. The value status of the inputs is assigned to bits 0
to 3 in input byte x + 1. The value status of the outputs is assigned to bits 0 to 7 in input byte
x + 2. This additional information provides information regarding the validity of the digital
values or channel status.
Bit = 1: No error on channel.
Bit = 0: Error on channel.
If the channel is configured as input, this means:
•
Short-circuit to ground at sensor supply or
•
Parameter error
If the channel is configured as output, this means:
•
Short-circuit of output to ground or
•
Parameter error or
•
For channels 4 ... 7: Missing load voltage 2L+