Functions
5.1 Connecting other bus systems
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
121
5.
Assign the interface module to the IE/PB Link.
Figure 5-3
Configuring an IE/PB link
6.
Select the IE/PB Link PN IO in the network view of STEP 7.
7.
In the Inspector window, go to the "Gateway" area and select the "Network gateway as
PROFINET IO proxy" option.
Figure 5-4
Setting a gateway
8.
In the PROFINET device number area, you can assign a PROFINET device number for the DP
slave.
If you have selected the "Device number = PB address" check box (default), STEP 7
automatically assigns the device number according to the PROFIBUS address of the slave. In
addition, you no longer need to update the device number if the PROFIBUS address changes.
Figure 5-5
Assigning PN device numbers for IE/PB link
Result
You have connected the DP slave to the PROFINET IO system.
Reference
Additional information on the IE/PB link is available in the manual Gateway IE/PB Link PN IO
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......