Interrupts/diagnostic alarms
5.2 Interrupts
IO-Link digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BL0)
Equipment Manual, 08/2021, A5E47926730-AB
19
5.2
Interrupts
The DQ 8x24VDC/2A 8xM12 IO-Link digital output module supports diagnostic interrupts.
Diagnostic interrupt
The digital output module generates a diagnostic interrupt at the following events:
•
Short-circuit of outputs to ground
•
Load voltage 2L+ missing or too low
5.3
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the LED DIAG flashes red on the
digital output module. You can read out the diagnostics alarms, for example, from the status
of the IO-Link master. You can evaluate the error codes with the user program.
Table 5- 4
Diagnostics alarms, their meanings and corrective measures
Diagnostics alarm Error code Meaning
Remedy
Short-circuit
0x7711
Short-circuit of an output to
ground
Eliminate the short-circuit
Load voltage 2L+
missing
0x5112
Load voltage 2L+ missing or too
low
•
Check the supply voltage
•
Check the module
Summary of Contents for SIMATIC ET 200AL