Diagnostics alarms
5.2 Diagnostics alarms
CM 4xIO-Link 4xM12 (6ES7147-5JD00-0BA0)
Equipment Manual, 04/2021, A5E32352322-AE
29
Diagnostics
alarm
Error
code
Meaning (IO-Link error code)
IO-Link
master
IO-Link
device
Safety shutdown 19
H
• Serious error (master has to be replaced) (1880
H
)
X
External fault
1A
H
• Error during data backup (1809
H
, 180A
H
, 180B
H
, 180C
H
, 180D
H
)
• More than six errors are pending simultaneously on the IO-Link
device (1808
H
)
• Consistency error in electronic coding element (1885
H
)
• Process data length exceeded (1887
H
)
X