Product overview
2.3 Functions
IM 157-1 PN (6ES7157-1AB00-0AB0)
Equipment Manual, 05/2021, A5E32347036-AE
21
2.3.2.4
PROFIenergy control data records
PROFIenergy control data records
The control data record for PROFIenergy, Index 80A0
H
, supports the following services for the
IM 157-1 PN interface module:
Table 2- 5
Control data records for PROFIenergy
Service
Service ID
Meaning
Start pause
1
01
H
Assuming the configured Pause behavior, suppressing all
associated diagnostics data
End Pause
02
H
Leaving the pause
Query Modes
03
H
Reads the supported modes
•
Request List Energy Saving Modes
•
Request Get Mode (Energy Saving Mode Data)
PEM status
04
H
Reading the PROFIenergy status
PE_Identify
05
H
Reading the supported PROFIenergy services
1
The minimum (configurable) pause time for the ET 200AL distributed I/O system is 10 s.
2.3.3
Configuration control (option handling)
Properties
Configuration control allows you to prepare your distributed I/O system for future extensions
or options. Configuration control means that you can configure the planned maximum
configuration of your distributed I/O system in advance and vary it later in a flexible manner
by means of the user program.
Reference
You can find more information on configuration control
•
In the system manual ET 200AL Distributed I/O System
https://support.industry.siemens.com/cs/ww/en/view/89254965
•
On the Internet under the following link: Application collection
https://support.industry.siemens.com/cs/ww/en/view/29430270
).
•
In the STEP 7 online help.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......