Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
34
Function Manual, 11/2019, A5E33454822-AC
Status parameter
Error codes or status information is output as double word at the Status output.
The double word is divided as follows:
Error code
Meaning
(DW#16#...)
z0yywwww
Error of a system function:
•
during startup (z = 1)
•
during normal operation (z = 0)
System functions with subordinate use are coded in yy: See table with error codes.
wwww specifies the RET_VAL of the system function. The error information is available in the help for the
system function.
z0yy0000
An error that does not originate in a system function. This error receives a consecutive error number yy.
The error can occur:
•
during startup (z = 1)
•
during normal operation (z = 0)
Table with error codes
Error code
Meaning
Solution
(DW#16#...)
00000000
No error.
—
1001xxxx
An error has occurred with system function RD_SINFO.
The low word xxxx displays the error information of the
RET_VAL return value from RD_SINFO.
•
Read the description of the RD_SINFO in the
STEP 7 (TIA Portal) information system.
•
Make sure that TIO_SYNC is called in a
"Synchronous Cycle" or "MC-PostServo"
OB.
10020000
The read cycle time of the isochronous OB is invalid
(LT#0ms or negative).
The instruction can only be used without errors in an
isochronous OB.
•
Correct the value of the cycle time.
•
Make sure that TIO_SYNC is called in a
"Synchronous Cycle" or "MC-PostServo"
OB.
10030000
The TIO_SYNC instruction is not called in an isochronous
OB. The instruction can only be used without errors in an
isochronous OB.
Make sure that TIO_SYNC is called in a
"Synchronous Cycle" or "MC-PostServo" OB.
10040000
The assigned value at the PIP_Mode input parameter is
outside the valid range of 0 to 2.
Correct the value at the PIP_Mode input
parameter.
10050000
The configured send clock is outside the permitted range
of 0 < SendClock <= 4 ms.
Correct the value of the send clock.
0006xxxx*
An error has occurred during execution of the SYNC_PI
system function. The low word xxxx displays the error
information of the RET_VAL return value from SYNC_PI.
Read the description of the SYNC_PI in the
STEP 7 (TIA Portal) information system.
0007xxxx*
An error has occurred during execution of the SYNC_PO
system function. The low word xxxx displays the error
information of the return value RET_VAL from SYNC_PO.
Read the description of the SYNC_PO in the
STEP 7 (TIA Portal) information system.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......