Product overview
2.4 Fail-safe digital outputs
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
15
See also
Accessories for the ET200AL distributed I/O system
https://support.industry.siemens.com/cs/us/en/view/89254965
2.4
Fail-safe digital outputs
The digital outputs of the F-DI 4/F-DQ 2 Fail-Safe module are for use in fail-safe applications
and are suitable for various actuators such as the following:
•
Solenoid valves
•
DC contactors
•
Indicator lights
The two digital outputs each have P- and M-switches that are rated to connect 24 V DC
actuators with up to a 2.0 A rating. The two digital outputs use the load voltage 2L+ with a
maximum current of 4.0 A. This means that the total current usage by the two digital outputs
cannot exceed 3.96 A because the 2L+ supply uses about 40 mA.
Outputs
The fail-safe digital outputs consist of two output channels (F-DQ x.0 to x.1). You can use
each output for SIL 3 applications.
Connections
Output channel
X14
0
X16
1
Each output consists of two switches:
•
A P-switch connects 24 V DC positive (L+) to the load.
•
An M-switch connects the load to M or 24 V DC return.
Both switches must be ON for current to flow to the load.
The fail-safe digital outputs use two microcontrollers to implement the safety function. One
microcontroller controls the P-switch while the other microcontroller controls the M-switch.
Status of the P-switch is fed back to the other microcontroller (the one that controls the
M-switch). Likewise, status of the M-switch is fed back to the other microcontroller (the one
that controls the P-switch). The microcontrollers use the feedback to verify that the output
switches are operating properly and in the commanded state.
You must configure a "Maximum readback time" that specifies the allowed delay for the
output voltage to respond to the switch change.
The fail-safe digital outputs regularly test each P- and M-switch to verify that each switch is
still functional and under independent control. Your configured "Maximum readback time"
also sets the duration of the "OFF" test pulse. You must configure a "Maximum readback time
switch on test" which sets the duration of the "ON" test pulse. Choose these durations short
enough to not affect your load.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......