Functions
5.3 Shared device
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
173
3.
Place the I/O modules from the hardware catalog in a suitable slot.
4.
Add MSI/MSO submodules to the I/O modules:
–
Input modules: Select the number of MSI submodules under "Module parameters
" > "DI configuration" or "AI configuration" in the area "Copy of module for Shared
Device (MSI)".
–
Output modules: Select the number of MSO submodules under "Module parameters
" > "DQ configuration" or "AW configuration" in the area "Copy of module for shared
device (MSO)".
Figure 5-35 Configuring I/O modules with MSI/MSO
Assigning MSI/MSO submodules to an IO controller
You can assign the submodules in a shared device to an IO controller.
For more information, refer to Configuring shared device (Page 1).
Configuring access to a shared device and the module-internal shared input / shared output
(MSI /MSO) function
You can learn how to access a shared device and the MSI /MSO function in STEP 7 with this
FAQ (
https://support.industry.siemens.com/cs/ww/en/view/109736536