Technical specifications
IO-Link digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BL0)
Equipment Manual, 08/2021, A5E47926730-AB
21
Article number
6ES7142-5AF00-0BL0
Load resistance range
•
lower limit
12
Ω
•
upper limit
4 k
Ω
Output voltage
•
for signal "1", min.
L+ (-0.8 V)
Output current
•
for signal "1" rated value
2 A (45 °C); 1 A (55 °C)
•
for signal "1" permissible range, max.
2 A; with inductive load to IEC 60947-5-1, DC-13 /
AC-15
•
for signal "0" residual current, max.
0.5 mA
Switching frequency
•
with resistive load, max.
100 Hz
•
with inductive load, max.
0.1 Hz; 0.25 Hz at 25 °C
•
on lamp load, max.
1 Hz
Total current of the outputs
•
Current per module, max.
8 A
Cable length
•
unshielded, max.
30 m
IO-Link
IO-Link protocol 1.1
Yes
Transmission rate
38.4 kBd (COM2)
Cycle time, min.
2.1 ms
Size of process data, input per module
0 byte
Size of process data, output per module
1 byte
Supported IO-Link profiles
common profile
Cable length unshielded, max.
20 m
Connection of IO-Link devices
•
Port type A
Yes
Interrupts/diagnostics/status information
Substitute values connectable
Yes; channel by channel, parameterizable
Alarms
•
Diagnostic alarm
Yes; Parameterizable
Diagnoses
•
Short-circuit
Yes; Outputs to ground; module by module
Diagnostics indication LED
•
Channel status display
Yes; green LED
•
for module diagnostics
Yes; green/red LED
•
For load voltage monitoring
Yes; green LED
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......