Diagnostics of the S7-1500R/H redundant system
7.4 Diagnostics in the RUN-Redundant system state
Diagnostics
Function Manual, 11/2019, A5E03735838-AF
111
7.4
Diagnostics in the RUN-Redundant system state
Diagnostics view in redundant mode
Primary CPU and backup CPU are each in the RUN-Redundant operating state.
In the RUN-Redundant system state, the primary and backup CPU display the online data of
the redundant system irrespective of which of the two CPUs the online connection has been
made.
The diagnostics between the two CPUs is synchronized (diagnostics entries, diagnostics
events).
The "Alarm display" tab shows the alarms of the redundant system.
You can find more information in the Diagnostics view in the project tree and in the device
view and network view (Page 106).
No error in RUN-Redundant system state
If no error is detected in the RUN-Redundant system state, all diagnostics icons in the
project tree and in the network view show "No fault" .
Figure 7-11 Diagnostics example: No fault in the RUN-Redundant project tree