Parameters/address space
4.4 Address space
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
30
Equipment Manual, 08/2021, A5E32350124-AG
Configuration options of analog input module AI 4xU/I/RTD 4xM12
You have the following configuration options:
•
Configuration 1: without value status
•
Configuration 2: with value status
Evaluating the value status
If you enable the value status for the analog input module, a bit is also assigned in the input
address space. Bits 0 to 3 in this byte are assigned to a channel and provide information on
the validity of the analog value. The value status is independent of whether or not
diagnostics was configured.
Bit = 1: No error on channel.
Bit = 0: Error on channel.