Product Information for F-DI 4 + F-DQ 2x24 VDC/2A, 4xM12
2
A5E51082356-AA, V1.0 05/2021
Power cycling the module used with S7-300 F-CPUs
Statement of the problem
When the ET 200AL F-DI 4 + F-DQ 2 module is used with S7-300 F CPUs (PROFIsafe V2.4), there are certain power cycling
situations which can lead to the module powering up in an error state. If the system is operating in RUN state and either of
the following conditions occur, then the problem can occur:
•
The module is power cycled indpendently
•
The module and interface module (IM) are power cycled simultaneously
If the problem occurs
Perform one of the following actions to restore the module to normal operation:
•
Power cycle the IM independently
•
Power cycle the CPU independently
•
Download the hardware configuration to the F-CPU using STEP7 (TIA Portal) or Step 7 Classic
Steps to avoid the problem
The problem can be avoided by ensuring that for any situation in which the module is power cycled with the system in RUN
state:
•
The CPU and the IM are also power cycled simultaneously with the module, or
•
The CPU and/or the IM are power cycled independently after the module has completed its power cycle
Product Information for F-DI 4 + F-DQ 2x24 VDC/2A, 4xM12
A5E51082356-AA, V1.0 05/2021
Siemens AG
Digital Industries
Postfach 48 48
90026 NÜRNBERG
GERMANY
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......