Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
Function Manual, 11/2019, A5E33454822-AC
49
Error code
Meaning
Solution
(DW#16#...)
10060000
No TIO module found.
Possible cause:
The module configured using the hardware identifier is
not a TIO module.
•
Make sure that the configured module is a
TIO module.
•
Check the value at the HWID input
parameter. Specify the hardware identifier of
the TIO module from its module properties in
the hardware configuration.
10070000
An internal error occurred during the address calculation. Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO module
from its module properties in the hardware
configuration. An internal system constant of
data type Hw_SubModule is available for the
symbolic addressing.
00080000
TIO module is not synchronized using the TIO_SYNC
instruction.
The error code can also indicate that:
•
A job was already present before the first run of the
instruction.
•
The assigned number at the Channel input parameter
is not a digital input.
Check the instruction TIO_SYNC.
10090000
The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
APP
<= 16 ms and is therefore
invalid.
The instruction can only be used without errors in an
isochronous OB.
•
Correct the cycle time.
•
Make sure that TIO_DI_ONCE is called in a
"Synchronous Cycle" or "MC-PostServo" OB.
100A0000
The time T
O
of the TIO model stored in TIO_SYNC_Data
is outside the permissible range of 0 < T
o
<= 4 ms.
Check the instruction TIO_SYNC.
100Bxxxx
An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_ADDR.
Read the description of the RD_ADDR in the
STEP 7 (TIA Portal) information system.
000C0000
The converted time stamp is invalid.
Possible cause:
Communication error
Check the communication with the TIO module.
000D0000
The Quality Information of the digital input indicates that
an error has occurred at the digital input.
Check the supply voltage L+/1L+/2L+.
000E0000
The assigned number at the Channel input parameter is
not a digital input configured as Timer DI.
•
Check the channel configuration (only for
TM Timer DIDQ 16x24V).
•
Check the operating mode of the digital input.
000F0000
The assigned value at the EdgeSel input parameter is
outside the valid range of 1 to 5.
Correct the value at the EdgeSel input
parameter.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......