Technical specifications
10.5 Details on insulation, protection class, degree of protection and rated voltage
Distributed I/O system
108
System Manual, 08/2021, A5E31861578-AJ
10.5
Details on insulation, protection class, degree of protection and
rated voltage
Insulation
The insulation is designed in compliance with the requirements of IEC 61010-2-201.
Note
Galvanic isolation with 707 V DC (Type Test) is tested for modules with 24 V DC supply
voltage (SELV/PELV).
Pollution class according to IEC 61010-2-201
•
Protection class III
Severity for voltage interruption
The I/O devices of the distributed I/O system ET 200AL meet the severity class PS1 for voltage
interruption (5 ms).
Pollution degree / overvoltage category pursuant to IEC 61010-2-201
•
Pollution degree: 3
•
Overvoltage category: II
Degree of protection IP65 and IP67
Degree of protection IP65 and IP67 according to IEC 60529 for all modules of the ET 200AL
distributed I/O system:
•
1. Code number: Dust-proof and complete protection from contact
•
2. Code number: Protection from water
–
IP65: Protection from water jets from any angle
(The water may not have any damaging effect)
–
IP67: Protection against temporary submersion
(The water must not enter the enclosure in harmful quantities)
Rated voltage for operation
The following table shows the nominal voltage and the corresponding tolerance with which
the ET 200AL distributed I/O system operates.
Table 10- 12 Rated voltage for operation
Rated voltage (SELV/PELV)
Tolerance range
24 V DC
20.4 V to 28.8 V DC
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......