Digital output module DQ 8x24VDC/2A 8xM12 (6ES7142-5AF00-0BA0)
16
Equipment Manual, 08/2021, A5E36683723-AB
Parameters/address space
4
4.1
Parameters
The table below shows the parameters for the DQ 8x24VDC/2A 8xM12 digital output module.
Table 4- 1
Parameters
Parameters
Value range
Default
Scope
Diagnostics: Missing load voltage 2L+ •
Disable
•
Enable
Disable
Module
Diagnostics: Short-circuit to ground
•
Disable
•
Enable
Disable
Module
(Short-circuit of the
output to ground)
Reaction to CPU/master STOP
•
Shut down
•
Keep last value
•
Output substi-
tute value
Shut down
Module
Substitute value channel 0 … 7
•
0
•
1
0
Channel