Functions
5.3 Shared device
PROFINET with STEP 7
152
Function Manual, 05/2021, A5E03444486-AL
Setting of the real-time properties
STEP 7 calculates the communication load and thus the resulting update times. You must
enter the number of project-external IO controllers in the project in which the PROFINET
interface of the shared device is assigned to the IO controller so that a calculation is possible
with shared device configurations.
The maximum possible number of IO controllers for the shared device depends on the device.
This number is stored in the GSD file of the shared device.
You can set a very short send clock with a CPU as IO controller. The send clock can be shorter
than the shortest send clock supported by the shared device. In this case, the shared device is
operated by the IO controller with a send clock that it supports (send clock adaptation).
Example:
A CPU supports send clocks starting from 0.25 ms. A configured IO device also supports send
clocks starting at 0.25 ms; another IO device supports send clocks starting at 1 ms. In this
case, you have the option of setting the short send clock of 0.25 ms for the CPU. The CPU
operates the "slow" IO device with the send clock of 1 ms, for example.
Rules for the configuration
•
IO controllers that use the shared device are created in different projects. In each project,
care must be taken that the shared device is configured identically in each station. Only
one IO controller may ever have full access to a submodule. Inconsistencies in the
configuration result in a failure of the shared device.
•
If you have selected the "Use router" option for the IO controllers involved, you must have
set the same router address in all these IO controllers.
•
I/O addresses of a module or submodule can only be edited if a module or submodule is
assigned to the IO controller in the same project.
•
The shared device must have the same IP parameters and the same device name in each
project.
•
The send clock must be identical for all IO controllers that have access to the shared
device.
•
The S7 subnet ID of the subnet to which the shared device is connected must be identical
in all projects.
•
The following functions are only available if the PROFINET interface of the shared device is
assigned to the local IO controller:
–
IRT operation
–
Prioritized startup
–
Parameter assignment of the port properties
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......