OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
346
Function Manual, 05/2021, A5E03735815-AJ
To do this, follow these steps:
1.
If the client was configured in another project and you created and exported the client
certificate there:
–
Select the "Use global security settings for certificate manager" option in the local
certificate manager of the server. This makes the global certificate manager available.
You will find this option under "Protection & Security > Certificate manager" in the
properties of the CPU that is acting as server.
–
If the project is not yet protected, select "Security settings > Settings" in the STEP 7
project tree, click the "Protect this project" button and log on.
The "Global security settings" item is now displayed under "Security settings" in the
STEP 7 project tree.
–
Double click "Global security settings".
–
Double click "Certificate manager".
STEP 7 opens the global certificate manager.
–
Click the "Device certificates" tab.
–
Right-click in the tab on a free area (not on a certificate).
–
Select the "Import" shortcut menu.
The dialog for importing certificates is displayed.
–
Select the client certificate that the server is to trust.
–
Click "Open" to import the certificate.
The certificate of the client is now contained in the global certificate manager. Note
the ID of the client certificate just imported.
2.
Click the "General" tab in the properties of the CPU that is acting as server.
3.
Click "OPC UA > Server > Security > Secure Channel".
4.
Scroll down in the "Secure Channel" dialog to the section "Trusted clients".
5.
Double-click in the table on the empty row with "<add new>". A browse button is displayed
in the row.
6.
Click this button.
7.
Select the prepared client certificate.
8.
Click the button with the green check mark.
9.
Compile the project.
10.
Load the configuration onto the S7-1500 CPU (server).
Result
The server now trusts the client. If the server certificate is also considered trusted, the server
and client can establish a secure connection.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......