Wiring
3.3 Configuring PROFIBUS DP address and terminating resistor
IM 157-1 DP (6ES7157-1AA00-0AB0)
18
Equipment Manual, 08/2021, A5E32100641-AE
Setting the PROFIBUS DP address
Configurable PROFIBUS DP addresses are 1 to 99.
Proceed as follows to configure the PROFIBUS DP address:
1.
Remove the two M12 sealing caps from the rotary coding switches
(use 14 mm socket wrench, if needed).
2.
Configure the desired PROFIBUS DP address with a screwdriver on the rotary coding
switches.
–
Top rotary coding switch: Tens digit
–
Bottom rotary coding switch: Ones digit
3.
Screw the two M12 sealing caps back onto the thread to protect the rotary coding switches
(torque: 0.5 to 0.8 Nm).
4.
Switch the supply voltage off and on again (POWER OFF/POWER ON).
The figure below shows the rotary coding switches for configuring the PROFIBUS DP address.
①
Rotary coding switch for PROFIBUS DP (tens digit)
②
Rotary coding switch for PROFIBUS DP address (ones digit)
Figure 3-2
Setting the PROFIBUS address