Functions
5.7 Isochronous mode
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
223
5.7.4.2
Configuring isochronous mode on PROFINET IO
Introduction
The configuring of isochronous mode for a module is described as IO device in the following
based on the ET 200MP distributed I/O system. The procedure described also applies to other
distributed I/O systems (e.g., ET 200S or ET 200SP).
The IO controller is an S7-1500 CPU.
Requirements
•
The STEP 7 network view is open.
•
A S7-1500 CPU has been placed (e.g., CPU 1516-3 PN/DP).
•
An IM 155-5 PN HF interface module (ET 200MP) has been placed and networked with the
CPU via PROFINET IO.
•
All requirements for an IRT configuration are met:
–
The ports of the networked PROFINET interfaces of the CPU and interface module are
interconnected (topology configuration).
–
The RT class of the PROFINET interface of the interface module is set to "IRT" (area
"Advanced options > Real time settings > Synchronization").
–
The "sync master" and "sync slave" roles are assigned for the PROFINET interfaces of the
CPU and interface module (in the properties of a PROFINET interface: area "Advanced
options" > "Media redundancy" > "Domain settings").
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......