background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9023  Rev.2  P. 1 / 5

INSTRUCTION MANUAL

HIGH-SPEED DC VOLTAGE/CURRENT INPUT MODULE

(4 points, isolated)

MODEL

R30SVF4

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

High-speed DC voltage/current input module ...................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

GENERAL PRECAUTIONS

• Before you remove the terminal block or mount it, turn off 

input signals for safety.

 

HOT SWAPPABLE MODULES

• It is possible to replace a module with the power supplied 

provided that the module is replaced with one with the 
same model number and installed in the same base slot.

• Turn off input signals before replacing the module for 

safety.  Note that replacing multiple modules at once may 
greatly change line voltage levels.  We highly recommend 
to replace them one by one.

 

UNUSED CHANNEL

• Set unused channels to “CH disabled” with PC Configura-

tor software: R30CFG.  When input range is 1 to 5V DC 
or 4 to 20mA DC, input values of the unused channels left 
open are to be lower than -15%, which set a data error at 
the PLC or other host devices. 

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 10 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

• Be sure to attach the terminal cover for safety.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for R30SVF4

Page 1: ... input signals for safety HOT SWAPPABLE MODULES It is possible to replace a module with the power supplied provided that the module is replaced with one with the same model number and installed in the same base slot Turn off input signals before replacing the module for safety Note that replacing multiple modules at once may greatly change line voltage levels We highly recommend to replace them on...

Page 2: ...bus operate normally Blinks in 1 sec cycles with input value error 15 115 Blinks in 400 msec cycles with input circuit error AD converter response failure ON with internal bus error TERMINAL ASSIGNMENTS 11 VH1 12 COM1 13 VH2 14 COM2 15 NC 16 VH3 17 COM3 18 VH4 19 COM4 20 NC 1 VL1 2 I1 3 VL2 4 I2 5 NC 6 VL3 7 I3 8 VL4 9 I4 10 NC NO ID FUNCTION NO ID FUNCTION 1 VL1 Narrow span volt 1 11 VH1 Wide spa...

Page 3: ...O slot is vacant blank data is sent or received to from the PLC etc PWR COM I O1 I O n HOW TO MOUNT THE MODULE 1 Engage the positioning guide of the module with the In stallation Base 2 Pivot the module on the positioning guide and press it down until the lock tab clicks into place Positioning Guide 3 Tighten the base fixing screw using a screwdriver stem length 70 mm 2 76 or more torque 0 5 N m B...

Page 4: ...4 13 VH2 VL2 I2 COM2 4 14 3 16 VH3 VL3 I3 COM3 7 17 6 Input Connection Examples VHn In COMn VLn Wide Span Voltage Narrow Span Voltage Current VHn In COMn VLn VHn In COMn VLn Note Connect either wide or narrow span or current terminals for each channel Note Be sure to close across VLn and In terminals for a current input Input 1 Input 2 Input 3 Input 4 INTERNAL POWER INTERNAL BUS BUS CONNECTOR INPU...

Page 5: ...nal block is separable in two pieces Evenly loos en two screws on top and bottom of the terminal block to separate PC CONFIGURATOR The following parameter items can be set with using PC Configurator Software model R30CFG Refer to the users manual for the R30CFG for detailed op eration of the software program CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING Unused setting CH enabl...

Reviews: