Eaton Logic Controller

 

Ethernet Distributed I/O Adapter 

Module

 

INSTRUCTION SHEET

 

 

[Applicable Distributed I/O Adapter Module] 

ƒ

 ELC-CAENET 

 

 

 

 

 

   

IL05006001E 
002-1214120-01 

 

Summary of Contents for ELC Series

Page 1: ...2010 12 03 5011696801 ETP1 Eaton Logic Controller Ethernet Distributed I O Adapter Module INSTRUCTION SHEET Applicable Distributed I O Adapter Module ELC CAENET IL05006001E 002 1214120 01...

Page 2: ...t unless power has been switched off or the area is known to be non hazardous a DO NOT connect AC power to any of the DC input output terminals as it will damage them Check all wiring prior to power u...

Page 3: ...icator on ELC CAENET is ON 2 Analog I O modules in RUN status 3 Smart PLC function is running RUN STOP 1 Analog I O modules switch from RUN to STOP status 2 Output points on digital I O modules are al...

Page 4: ...ransmission Rate 10 100 Mbps Auto Detect Protocol ICMP IP TCP UDP DHCP NTP HTTP MODBUS TCP EtherNet IP RS 232 Interface Interface RS 232 Number of Ports 1 Port Transmission Cable ELC CBPCELC3 RS 485 I...

Page 5: ...re 5 95 humidity Vibration Shock Resistance Standard IEC61131 2 IEC 68 2 6 TEST Fc IEC61131 2 IEC 68 2 27 TEST Ea Certificates Installation How to connect extension modules to the ELC CAENET 1 Adjust...

Page 6: ...on Codes Supported Exception code Explanation 0x01 Illegal function 0x02 Illegal data address 0x03 Illegal data value 0x04 Slave device failure 0x0A Gateway path unavailable 0x0B Gateway target device...

Page 7: ...t Object Discrete Output Object BR Object RCR Object TCP IP Interface Object Ethernet Link Object 0x10 Set Attribute Single Assembly Object Discrete Output Object BR Object RCR Object 0x4E Forward Clo...

Page 8: ...tched to RUN BAT LOW Red constantly OFF The battery is normal None Red flashes The battery is in low voltage Check the battery RS 232 Yellow flashes Data is being transmitted in the serial port None Y...

Page 9: ...connection Check if the number of connections exceeds the maximum F7 Flash RS 485 setting error Check if the RS 485 communication format is correct F8 Flash IP setting error 1 DHCP request failure 2 I...

Page 10: ...le to locate a module Not connected to the network Check if ELC CAENET is correctly connected to the network Unable to locate a module The computer is blocked by the firewall Search by IP address or u...