Mounting
4.2 Mounting modules
IO-Link I/O modules
20
System Manual, 08/2021, A5E48755395-AB
Drill holes of the modules
All IO-Link I/O modules have a uniform drill pattern.
•
All module housings are axisymmetrical.
•
The distance between the top and bottom drill hole is identical for all modules.
Mounting 30 mm wide I/O modules (front or side)
Watch video sequence (
https://support.industry.siemens.com/cs/ww/en/view/95886672
The 30 mm I/O modules have a fastening point at the top and bottom. The 30 mm wide
I/O modules can also be side-fastened. When fastening them at the side, you must use the
supplied spacers.
Follow the steps below to mount a 30 mm wide I/O module:
1.
Drill two fastening holes with 4.5 mm diameter spaced 149.6 mm apart.
2.
Use the supplied spacers for side fastening of the I/O module on the top and bottom (on one
side adjacent to the fastening surface).
3.
Fasten the I/O module with the screws to both fastening points (tightening torque 1.2 Nm).