Open User Communication
6.7 Setting up communication with Modbus TCP
Communication
Function Manual, 05/2021, A5E03735815-AJ
131
4.
Assign the parameters of the MB_CLIENT or MB_SERVER instruction. Observe the following
rules:
An IPv4 server address must be specified for each MB_CLIENT connection.
Each MB_CLIENT or MB_SERVER connection must use a unique instance DB with one of
the data structures TCON_IP_v4, TCON_QDN or TCON_Configured.
Each connection requires a unique connection ID. The connection ID and instance DB
belong together in pairs and must be unique for each connection.
Figure 6-9
MB_CLIENT
Figure 6-10 MB_SERVER
5.
Download the hardware configuration and user program to the CPU.