Supported functions
7.1 Calibrating analog modules
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
107
The respective manual will include information whether or not your analog module supports
the "Calibration" functionality.
Scope of functions
The "Calibration" group offers the following functions:
● Specifying the current calibration of all channels
● Calibrating a channel
● Canceling a running calibration
● Resetting the calibration of a channel to the factory settings
7.1.2
Calibrating analog modules
Manual calibration
The following requirements must be met to start manual calibration:
● An online connection exists between STEP 7, the respective CPU and the analog module
to be calibrated.
● You have opened the "Online & Diagnostics" view for the selected analog module from
the shortcut menu of the project and you are now in the "Functions > Calibration" area.
● The configuration reflects the actual structure of the station.
● No calibration process is busy on the module (if you want to launch calibration).
● A 24 V load voltage must be present at each module for the calibration.
● The last step was successfully completed (if you want to continue or conclude
calibration).
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......