Connecting transducers
4.5 Wiring current transducers
Analog value processing
Function Manual, 06/2014, A5E03461439-AC
73
Wiring 2-wire transducers to an analog input for 4-wire transducers
The figure below shows an alternative to the above connection: supplying the 2-wire
transducer from supply line L+ of the module. If you use this type of connection, you will
need to set the "Current (4-wire transducer)" measurement type in STEP 7.
In this type of connection, galvanic isolation between the supply voltage L+ and the analog
circuit will be removed.
①
2-wire transducers (2WT)
②
Equipotential bonding cable (only relevant to modules with M
ANA
connection)
Figure 4-5
Example: Wiring 2-wire transducers to an analog input for 4-wire transducers
Wiring and connecting 4-wire transducers
4-wire transducers provide terminals for connecting a separate supply voltage. They are
powered with an external supply and are frequently called "active transducers". If you use
this type of connection, you will need to set the "Current (4-wire transducer)" measurement
type in STEP 7.
①
4-wire transducers (4WT)
②
Equipotential bonding cable (only relevant to modules with M
ANA
connection)
Figure 4-6
Example: Wiring 4-wire transducers to an analog input module
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......