Interrupts/diagnostic messages/diagnostics
6.5 Fault types, causes, and corrective measures
Digital I/O module F-DI 4+F-DQ 2x24VDC/2A, 4xM12 (6ES7146-5FF00-0BA0)
Equipment Manual, V1.0, 05/2021, A5E51082342-AA
75
Event ID
Diagnostic
message
F-DI 4/F-DQ 2
Fail-Safe
module
Description
Possible causes
Corrective measures
1
16x0306 Internal sensor
supply short-
circuit to P
F-DI 4/F-DQ 2
digital inputs
Module-provided sen-
sor supply voltage
shorted to P
•
Sensor supply
shorted to P
•
Short-circuit test
duration config-
ured too short
•
Failed sensor sup-
ply
•
Eliminate the short-
circuit
•
Increase short-
circuit test duration
•
Replace the fail-
safe module
16x0307 Overload or inter-
nal sensor supply
short-circuit to
ground
F-DI 4/F-DQ 2
digital inputs
Internal sensor supply
voltage shorted to M,
ground, or excessive
load on sensor supply
•
Short-circuit
•
Excessive load on
sensor supply
•
Failed sensor sup-
ply
•
Eliminate the short-
circuit
•
Reduce load on
sensor supply
•
Replace the
fail-safe module
16x030D F-address
memory not ac-
cessible
Module
The memory where
the F-address is stored
is not accessible
•
eCoding plug is
missing
•
eCoding plug is
defective
•
Install an eCoding
plug into X40 of
the module
•
Replace the defec-
tive eCoding plug
16x030E No valid F-address
available
Module
Fail-safe address is not
valid (F-address and
CRC inconsistent)
•
eCoding plug has
never been as-
signed a PROFIsafe
address
•
eCoding plug is
defective
•
Assign the PROFIs-
afe Address
•
Replace the eCod-
ing plug
16x0311 Frequency too
high
F-DI 4/F-DQ 2
digital outputs
Switching frequency
exceeded; readback
not in time
Process value from
safety program
changing too rapidly
for module to follow
Change Safety pro-
gram logic to guaran-
tee more time
between output
changes
16x0312 Undertempera-
ture
Module
•
Under-temperature
at microcontrollers
•
Under-temperature
at I/O
Shutdown due to
violation of low
temperature limit
value in the module
case
•
Check the ambient
temperature
•
Once the fault
has been eliminat-
ed, switch the
power off and on
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......