Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
46
Equipment Manual, 08/2021, A5E48753535-AB
Representation of analog values
B
B.1
Representation of analog values in voltage measuring range
The table below lists the decimal and hexadecimal values (codes) of the voltage measuring
range.
Table B- 1
Voltage measuring range ± 80 mV
Values
Voltage measuring range
Range
Dec.
Hex.
± 80 mV
32767
7FFF
> 94.1 mV
Overflow
32511
7EFF
94.1 mV
Overrange
27649
6C01
27648
6C00
80 mV
Nominal range
20736
5100
60 mV
1
1
2.89 µV
0
0
0 mV
-1
FFFF
-2.89 µV
-20736
AF00
-60 mV
-27648
9400
-80 mV
-27649
93FF
Underrange
-32512
8100
-94.1 mV
-32768
8000
< -94.1 mV
Underflow