Accessories/spare parts
C.2 Cables
Distributed I/O system
122
System Manual, 08/2021, A5E31861578-AJ
The following table shows the technical properties of the connecting cable for ET-Connection
standard.
Table C- 10 Connecting cables for ET-Connection
General information
Product type designation
CONNECTING CABLE FOR BUS CABLE ET-
CONNECTION, CABLE 0.2 M
Function
To connect two bus cables ET-CONNECTION
Degree of protection and protection class
IP65
Yes
IP67
Yes
Ambient conditions
Ambient temperature during mounting
minimum
-30 °C
maximum
80 °C
Storage/transport temperature
Ambient temperature during transport and storage
minimum
-40 °C
maximum
80 °C
Cables
Cable designation
2Y(ST)CY 1x4x0.5/1.0-100-GN
Number of electrical wires
4
Design of shielding
Overlapped aluminum-lined sheet, coated with
shielding made of tin plated copper wires
Cable length
0.2 m
Outside diameter of the inner conductor
0.5 mm
Outside diameter of the wire insulation
1.0 mm
Outside diameter of the cable sheath
5 mm
Permissible bending radius
One time bending, min.
20 mm
Multiple bending, min.
40 mm
Constant bending
100 mm
Color of the cable sheath
Green
Color of the wire insulation of the data wires
White, yellow, blue, orange
Weight per length
34 kg/km
Mechanics/material
Type of cable outlet
180° cable outlet
Connector housing material
Metal
Wire insulation material
PE
Cable sheath material
PVC
Material property halogen free
No
Material property silicon free
Yes
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......