Functions
5.10 Standard machine projects
PROFINET with STEP 7
264
Function Manual, 05/2021, A5E03444486-AL
5.
Startup the S7-1500 system and call again the instruction "ReconfigIOSystem". Select MODE
2 to transfer the data record CTRLREC.
6.
Following successful transfer of the data record, call again the instruction
"ReconfigIOSystem". Select MODE 3 to activate all IO devices forming part of the current
configuration.
Result:
The CPU
activates
the following IO devices:
–
All IO devices that you have not set as optional IO devices.
–
All optional IO devices listed in the control data record (CTRLREC).
The following IO devices remain
disabled
:
–
Docking units (IO devices changing during operation).
–
Optional IO devices that are not listed in the control data record.
Note
Call the instruction "ReconfigIOSystem" for all values of the parameter MODE with the same
control data record (CTRLREC)!
If you use different data records for the values of the MODE parameter, this results in an
inconsistent customization of the configuration and thus to rather incomprehensible error
messages.