Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 4xM12 (6ES7144-5KD50-0BA0)
22
Equipment Manual, 08/2021, A5E48753535-AB
Parameter
Value range
Default
Effective range with config-
uration software e.g. STEP 7
(TIA Portal)
Reference junction •
Fixed reference tempera-
ture
•
Dynamic reference tem-
perature
•
Internal reference junc-
tion
•
No compensation
Internal refer-
ence junction
Channel
Channel
Fixed reference
temperature
-2290 ... 3276
0
Channel
Module
Smoothing
•
None
•
Weak
•
Medium
•
Strong
None
Channel
Channel
Interference fre-
quency suppression
•
60 Hz (16.6 ms)
•
50 Hz (20 ms)
1
•
16.6 Hz (60 ms)
50 Hz (20 ms)
1
Channel
Channel
Diagnostics:
Reference junction
•
Disable
•
Enable
Disable
Channel
Channel
Diagnostics:
Wire break
•
Disable
•
Enable
Disable
Channel
Channel
Diagnostics
Overflow/underflow
diagnostics
•
Disable
•
Enable
Disable
---
Channel
Diagnostics:
Underflow
•
Disable
•
Enable
Disable
Channel
---
Diagnostics:
Overflow
•
Disable
•
Enable
Disable
Channel
---
Conductor re-
sistance [m
Ω
]
2
0 ... 50000 m
Ω
0
Channel
---
Hardware interrupt
high limit 1
•
Disable
•
Enable
Disable
Channel
---
Hardware interrupt
low limit 1
•
Disable
•
Enable
Disable
Channel
---
Hardware interrupt
high limit 2
•
Disable
•
Enable
Disable
Channel
---
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......