Diagnostics of the S7-1500R/H redundant system
7.4 Diagnostics in the RUN-Redundant system state
Diagnostics
Function Manual, 11/2019, A5E03735838-AF
115
Evaluate diagnostics on the display
For example 2, display of the PLC_2 CPU shows:
●
In the "Overview" menu command: A message is available in the next lower level page.
●
In the "Diagnostics" menu command: A message is available in the next lower level page.
●
In the Module menu command: An error has occurred.
To evaluate the display, proceed as follows:
1.
Navigate to "Pairing state" via the menu commands "Overview" > "Redundancy".
2.
This is displayed as the pairing state: Single paired (X4).
This means that the redundancy connection is available at the H-Sync interface X4, but
not at the X3.
3.
Navigate to "Alarms" via the "Diagnostics" menu command.
4.
View the details of the alarm (evaluate diagnostics buffer).
S7-1500H Example 3:
A redundancy connection in S7-1500H is interrupted.
Evaluating diagnostics via X3 and X4 LEDs on the CPU
The LED X4 on CPU PLC_1 does not light up. This means:
●
The redundancy connection on the synchronization module was interrupted at the H-Sync
interface X4.
or
●
There is no synchronization module at the H-Sync interface X4.
Summary of Contents for SIMATIC ET 200AL
Page 2: ......
Page 143: ......
Page 218: ......
Page 250: ......
Page 296: ......
Page 337: ......
Page 365: ......
Page 392: ......
Page 419: ......
Page 451: ......
Page 483: ......
Page 597: ......
Page 648: ......
Page 702: ......
Page 739: ......
Page 781: ......
Page 804: ......
Page 828: ......
Page 853: ......
Page 880: ......
Page 906: ......
Page 996: ...Diagnostics ...
Page 1121: ......
Page 1565: ......