Mixed configuration
Equipment Manual, 11/2020, A5E33344611-AD
27
Configuring
7
Introduction
The mixed configuration allows the connection of up to 16 ET 200AL I/O modules to the
ET 200SP via ET-Connection. The figure below shows the configuration of the ET-Connection
and the assignment of the slots.
①
ET 200SP I/O modules
⑤
1st ET 200AL I/O module
②
ET 200SP server module
⑥
16th ET 200AL I/O module
③
Slots
⑦
ET-Connection
④
PROFINET IO
Figure 7-1
Mixed configuration
For more information about connecting ET-Connection, supply voltages, actuators and
sensors, refer to the ET 200AL system manual.
Configuration with a CPU
In a configuration with a CPU, a maximum of 2 slots can be used immediately to the right of
the CPU with CM DP module or Ethernet CP. Combinations are also possible, i.e. CM DP
module and one Ethernet CP or two Ethernet CPs.
BU-Send and BA-Send should always be inserted to the immediate right of the CM/CP.